WOOD GASIFYINGBOILERATTACK DPX STANDARD, PROFI, LAMBDAATTACK, s.r.o. - aktualizácia 05/2010SKENDERUFRESRO
10 ATTACK DPX LAMBDA 1. – Green control light 2. – Yellow Green control light 3. – Red Green control light 4. - Display 5. – Button „+“ 6. – Button
11 Purpose of usage Ecological warmwater boiler Ecological warmwater boiler Attack DPX is designed for heating of dwelling houses and similar objec
12 damaged. Creation of tar and condensate in the feed hopper is a phenomenon accompanying wood gasifying. If the boiler was out of order for a longer
13 of wood rises, output is lower than demanded and the service life of boiler as well as that of flue is shortened. If the draft is as specified,
14 thermostat. In case the temperature in the boiler does not exceed 65 °C in 2 hours of burning up time, the regulator stops the flue gas ventilato
15 Boiler overheating If the temperature of the boiler raises to more than 105 °C, the regulator stops the flue-gas fan and the control light of
16 Technical description of the ATTACK DPX LAMBDA: Combustion regulation The boiler output is regulated by means of the exhaust temperature – to the
17 Functions and text display at heating-up or refuel After pressing the button “+” (see button 5 in chap. 1.3), starts the process that includes foll
18 Temperature reaches 299°C and less, the exhaust fan is switched on again. This is protection against exhaust fan and/or the exhaust sensor damage.
19 Menu Submenu Indication Boiler set to °C -- Shows adjusted temperature of water in boiler. Boiler temperature °C
2 ATTACK DPX - Wood gasifying boiler - Assembly, control heat up and attendance training is perfomed by field engineer trained by pr
20 Settings for the commission of the ATTACK DPX LAMBDA . The start-up of device is enabled, when the minimum requirements for test- or heating opera
21 a difference between flue gas temperature and temperature in the boilers 06 : Disconnection O2
22 Cancelling of the manufacturer´s function This process requires code of manufacturer. It is possible to set operation hours of the boiler, to re
23 Selection Submenu Svítí Information Scale of O2 End of the test (+,-) After pressing the „+“ button, „calibrate“ appears on dipslay. Calib
24 automatically. During this test, it is necessary to hold the + button within 30 seconds, to prevent automatic stop of the test (see explanation in
25 remove the packing cord from the rabbet by a screwdriver. Remove the nozzle body and clean the holder thoroughly from the tar and old lute. Put the
26 is guaranteed for maximum moisture content of 20%. Guarantee expires at boiler operation with cut wood with humidity over 20%. Energy content of
27 space of min. 1meter. This space is necessary for basic operation, maintenance and service of the boiler. Location of the boiler in the dwelling sp
28 Boiler connection to the electricity mains The boiler is connected to the mains of 230 V/50 Hz by a supply cord and plug. The voltage is of M type
29 Regumat consists from three way mixing valve, circuitingpump, closing valve, thermometers and isolation. This solution is advantegeus because its c
3 - the mixing device Regumat ATTACK-OVENTROP is not installed in the system to ensure temperature of return water into boiler at least a
30 Obligate norms for projecting and assembly of boilers: STN EN 303-5 Solid fuel boilers for heating STN 73 42 10 Manufacturing of chimneys and f
31 Installation and exchange of fireproof adapting pieces Put the rear part into the lower chamber, the intagliated part backwards. It is necessary
32 Connection schemes Scheme of connection with regulation system REGUMAT ATTACK-OVENTROPBOILERATTACKExpansion tankPumpRegumatATTACK--OVENTROPHeatin
33 Connection with heat accumulators Connection system is based on principle of heating up of water in accumulation tanks, where the warmth is gradu
34 Advantages Boiler installation with accumulation tank brings several advantages: - lower fuel consumption (up to 30%). Boiler works at full output
35 Liquidate the packaging by repurchase / collection of raw materials, respectively use regulated dumping ground. Accessories The ATTACK DPX bo
36 Possible faults and methods of their deletion Fault Cause Solution Control light „Net“ does not lighti No voltage in mains Incorrectly plugged
37 Errors and warnings with the ATTACK DPX LAMBDA system By following errors and warnings it is not possible to burn in the boiler: - red display 3 l
38 Too high flue gas temperature (warning) Cause: Control light 3 red: Flue gas temperature > 300°C Flickers Temperature of flue gas is too high B
39 Antifreeze protection (warning) Cause: Control light 2 yellow: Correction: Reset: Boiler temperature is < 7°C, when the boiler is switched off
4 Manual content: 2. Important 4. Content 5. Introduction, general description 6. Technical parameters 7. Boiler dimensions 8,9, 10. Instrument
40 off by the flue gas sensor temperature decreases for 25% within 15 minutes, the boiler is switched off. The STB is started Residual warmth of
41 Table of dependence of resistance on temperature of the thermal probe of heating water (Profi version) Temperature °C MIN Resistance kOhm MAX
42 Electrical schemes of connection of the ATTACK DPX STANDARD, PROFI, LAMBDA boilers
44 ATTACK DPX LAMBDA Connection to the network from the bottom side of regulator FUSESENSORNETWORKPROTECTION CONDUCTORBOILERSWITCHING CONTACTWITHOU
45 Oxygene probe (Lambda sonda) 4-conductor silicone-covered flexicord with conductor´s crossection of 0,75mm2 white = warming 12Vblack= + signal of p
46 Elektric voltage 230V Grounding of covering Network cordPhaseGroundingZero conductorNetwork breaker max. 10A3-conductor flexicord 1,
47 ORIGINAL ES DECLARATION OF CONFORMITY NR. POZ-003/110110 Producer: Rudolf Bakala, corporate representative of the company DIELENSKÁ KRUŽNÁ 5020
48 European directives: 2004/108/ES, 2006/95/ES, 2006/42/ES Certificates: E-30-01097-09 z 30.11.2009 E-30-01096-09 z 30.11.2009 Last to digits of the
49 Notes
5 Introduction: Dear customer, thank you for confidence that you showed us by purchasing our product - the ATTACK wood gasifying boiler. We wish yo
51 Tel: 00421 43 4003 101Fax: 00421 43 4003 106E-mail: [email protected] [email protected]: www.attack.skATTACK, s.r.o.Dielen
6 Technical parameters: Boiler type DPX15 DPX25 DPX30 DPX35 DPX40 DPX45 Boiler output kW 15 25 30 35 40 45 Surface of exchanger m² 1,98
7 Dimensions of the ATTACK DPX boilers DPX15 DPX25 DPX30 DPX35 DPX40 DPX45 C.H. flow connection – „E“ G6/4“ G6/4“ G6/4“ G6/4“ G2“ G2“ C.H
8 Instrument panel ATTACK DPX STANDARD The wood gasifying boiler "ATTACK DPX Standard" is controled by boiler and flue gas thermostat.
9 ATTACK DPX PROFI The ATTACK DPX Profi version in comparison with Standard version represents higher attendance comfort, possibility of output modu